Mendota E-FV44I ECHO SERIES Operations Instructions Page 49

  • Download
  • Add to my manuals
  • Print
  • Page
    / 60
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 48
48
LP GAS PRESSURE REQUIREMENTS
Inlet and manifold gas pressure checking taps are located on gas valve. These ports are only accessible from the outer
left side of the fireplace. A qualified installer shall take pressure measurements at these ports to verify and set the correct
gas pressures during the LP Kit installation and before facia materials are installed over the front of this fireplace. Manifold
pressure must be taken at the “MANIFOLD PRESSURE" tap and inlet pressure at the "INLET PRESSURE" tap with the
burner operating by a qualified installer.
DESIRED
INLET
PRESSURE
MINIMUM
INLET
PRESSURE
MAXIMUM
INLET
PRESSURE
MANIFOLD
OUTLET
PRESSURE
AIR SHUTTER
POSITION
L.P. GAS
11.0" W.C.
(2.75 kPa)
11" W.C.
(2.75 kPa)
13.0" W.C.
(3.24 kPa)
10.0" W.C.
(2.5 kPa)
1/4" OPEN MIN.
(5 mm)
REGULATE THE FLAME HEIGHT TO "HIGH" POSITION. OUTLET GAS PRESSURES MAY VARY PLUS OR MINUS 5%.
LPG PROPER INPUT RATES:
With the proper orifices installed, as specified above, this
fireplace utilizing LP Gas will have a maximum input rate of
31,000 Btu/Hr.
LEAK TESTING REQUIREMENTS
Prior to completing the conversion process, check for gas
leaks with soap and water solution at all plumbing joints
prior to placing this appliance into operation. It is recom-
mended that all gas-plumbing joints, factory installed and
field installed are checked for leaks.
PILOT FLAME AND MAIN BURNER
RELATIONSHIP VERIFICATION
Prior to completing the conversion process, the qualified service technician must,
light the pilot light and verify the relationship between the pilot light flames and the
main burners. The pilot light flames directed towards the propagation ports on the rear and front burner must overlap the
propagation ports on the burners. The pilot light flames must be a minimum of ¾” long and must overlap the propagation
ports on both the rear and front burners as shown in the diagram, below. Verify that the burner tubes ignite quickly and the
burner flames propagate smoothly along the entire length of the burners.
PILOT FLAME LENGTH ADJUSTMENT
If the pilot light flame length is too short and the system does not maintain a standing pilot, a qualified installer may in-
crease the length of the pilot light flames to meet the two requirements: Minimum pilot light length to maintain a standing
pilot light and the pilot light flames must be long enough to overlap the front and rear burner ports.
Figure 1: Pressure Test Port
1" MIN.
FRONT
BURNER
REAR
BURNER
PILOT LIGHT FLAMES
MUST OVERLAP
BURNER PORTS.
Page view 48
1 2 ... 44 45 46 47 48 49 50 51 52 53 54 ... 59 60

Comments to this Manuals

No comments