GAS DIRECT VENT FIREPLACE
with Premium Fiber Log Set Combustion System
Model DXV-45 DT3 - LX
INSTALLATION & OPERATING INSTRUCTIONS
NO. DXV45-DT3-LX- 0812
WARNING
If you do not follow these instructions exactly, a fire or
explosion may result causing property damage, personal
injury or loss of life.
CAUTION: Keep gasoline and other liquids having flam-
mable vapors away.
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electrical switch; do not use any
phone in your building.
Immediately call your gas supplier from a neighbor's
phone. Follow the gas supplier’s instructions.
If you cannot reach your gas supplier, call the fire
department.
WARNING
Do NOT use this appliance if any part has been under water.
Immediately call a qualified service technician to inspect the
appliance and to replace any part of the control system and
any gas control, which has been under water.
AVERTISSEMENT. Quiconque ne respecte pas à la lettre
les instructions dans la présente notice risque de dé-
clencher un incendie ou une explosion entraînant des
dommages, des blessures ou la mort.
ATTENTION. Garder l’essence ou autres liquides produi-
sant des vapeurs inflammables loin del’appareil.
QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ :
Ne pas tenter d’allumer d’appareil.
Ne touchez à aucun interrupteur; ne pas vous servir
des téléphones se trouvant dans le bâtiment.
Appelez immédiatement votre fournisseur de gaz
depuis un voisin. Suivez les instructions du
fournisseur.
Si vous ne pouvez rejoindre le fournisseur, appelez
le service des incendies.
N’utilisez pas cet appareil s’il a été plongé dans l’eau,
même partiellement. Faites inspecter l’appareil par un
technicien qualifiéet remplacez toute partie du système
de contrôle et toute commande qui ont été plongés dans
l’eau.
AVERTISSEMENT : Une installation, un réglage, une modifi-
cation, une réparation ou un entretien mal effectué peut cau-
ser des dommages matériels ou des blessures. Voir la notice
de l'utilisateur quiaccompgne l’appareil. Pour de l’aide oueds
renseignements supplémentaires, consultez un installateur,
un technicien agréé ou le fournisseur de gaz.
WARNING: Improper installation, adjustment, alteration,
service or maintenance can cause injury or property damage.
Refer to this manual. For assistance or additional information
consult a qualified installer, service agency or the gas suppli-
er.
Page view 0
1 2 3 4 5 6 ... 55 56

Summary of Contents

Page 1 - GAS DIRECT VENT FIREPLACE

GAS DIRECT VENT FIREPLACE with Premium Fiber Log Set Combustion System Model DXV-45 DT3 - LX INSTALLATION & OPERATING INSTRUCTIONS NO. DXV45-DT3-

Page 2

9 INSTALLATION INSTRUCTIONS CAUTION: Each installation must conform to all local, state and national codes. Refer to the national fuel gas code an

Page 3 - INITIAL STARTUP ADVICE

10 GAS SUPPLY REQUIREMENTS Correct gas pressure and proper gas supply line sizing is imperative to the successful performance of your Mendota gas f

Page 4 - Contents

11 GAS PRESSURE REQUIREMENTS A MAJOR CAUSE OF OPERATING PROBLEMS WITH GAS APPLIANCES CAN BE IMPROPER GAS PRESSURE! Problems such as changes in flam

Page 5 - SPECIFICATIONS

12 EXTERIOR VENT LOCATIONS AND RESTRICTIONS Figure 3: Exterior Vent Locations NOTE: ALL MEASUREMENTS TO BE TAKEN FROM CENTER LINE OF VENT CAP ∨ -

Page 6 - ...CAUTION

13 HIGH ALTITUDE INSTALLATION INFORMATION: Prior to installing at altitudes higher than 7500, please con-tact the Mendota technical service departm

Page 7

14 HIGH ALTITUDE INSTALLATION INFORMATION: Prior to installing at altitudes higher than 7500, please con-tact the Mendota technical service departm

Page 8 - HEATING PERFORMANCE

15 5"/ 8"FLUE VENTING COMPONENTS FOR NG AND LPG ITEM # PART # DESCRIPTION 1 45-01-00222 12" VENT STACK 5" / 8" 1 45-01

Page 9

16 HIGH ALTITUDE INSTALLATION INFORMATION: Prior to installing at altitudes higher than 7500, please con-tact the Mendota technical service departm

Page 10 - INSTALLATION INSTRUCTIONS

17 A-1 MINIMUM RISE THROUGH-THE-WALL VENTING FOR NG AND LPG WARNING: ALWAYS USE HEAT SHIELD (#AA-11-00458) WHEN EXTERIOR WALL COVERING IS MADE O

Page 11 - GAS SUPPLY LINE SIZING

18 A-2 ELEVATED RISE THROUGH-THE-WALL VENTING FOR NG AND LPG The minimum vertical rise from top of fireplace is 48 in. when used with the maximum

Page 12 - GAS PRESSURE REQUIREMENTS

1 In the Commonwealth of Massachusetts: • Installation must be performed by a licensed plumber or gas fitter; • A CO detector shall be installed

Page 13

19 B - 1 VERTICAL THROUGH-THE-ROOF VENTING FOR NG AND LPG The maximum vertical run of vent pipe is 36 ft. from the top of the fireplace. The fir

Page 14 - WARNING

20 HIGH ALTITUDE INSTALLATION INFORMATION: Prior to installing at altitudes higher than 7500, please con-tact the Mendota technical service departm

Page 15

21 MENDOTA DESIGNER FRONTS INSTALLATION INFORMATION The following Designer Fronts are available for the DXV-45 Fireplace: 1. Andover Arched Doo

Page 16

22 HEARTH PAD SURFACE MUST BE FLUSH WITH FIREPLACE BOTTOMHEARTH PADSURFACEHearth Protection Pad Installation Information when planning to Install t

Page 17

23 2.) PULL3.) ROTATE4.) RELEASE1.) INSERTDOOR REMOVAL AND REPLACEMENT CAUTION: Do not operate the appliance with glass removed, cracked or broken.

Page 18 - HEAT SHIELD #AA-11-00458

24 GLASS FRAME ASSEMBLY REPAIR AND REPLACEMENT TO REPLACE DAMAGED GLASS Using an 1/8” drill bit, drill through 3 rivets on each side of glass fram

Page 19

25 DXV45 COAL BED AND LOGS INSTALLATION Carefully unpack the shipping boxes containing the coal bed sections and logs and remove them gently from t

Page 20

26 1. Locate Fiber Coal Bed “A”. This Fiber Coal Bed installs between the front burner and the front ofthe rear burner tube as shown below.2. The

Page 21

27 9. Identify Log “C”. Back left log.10. Locate holes on bottom of log.11. Place log “C” onto the 2 pins on left-side behind the rear burner as s

Page 22

28 18. Identify Log “G” and locate the hole at its bottom surface. Log “G” will be installed on the left side of the fireplace, with the hole on t

Page 23 - FLUSH WITH FIREPLACE BOTTOM

2 DXV45 DT3 FEATURES - QUICK REFERENCE INFORMATION EXTERNAL DIMENSIONS: 40-3/8” Wide X 39” High X 19-1/8” Deep MINIMUM FRAMING DIMENSIONS: 41” WID

Page 24 - DETAIL A

29 22. Identify Log “I”. Log “I” will be installed in the middle of the fireplace, with the hole on the bottom of the log setting on the middle pin

Page 25 - TO REPLACE DAMAGED GLASS

30 Place small coals between Firebox Front and front Burner. Pile the coals higher near the Front burner to build height. Any excess coals should

Page 26

31 FINAL LOG SET, COALS AND INSWOOL LAYOUT RECOMMENDED PATTERNNote: Some minor adjustment to coals locations may me necessary on LP gas units. Als

Page 27 - FIBER COAL BED “A”

32 The following Check Off Lists must be completed prior to final operation of the Fireplace. Failure to do so may result in abnormal function or d

Page 28

33 BEFORE YOU BEGIN Read this entire manual before you use your new fireplace. Failure to follow the instructions may result in property dam-age,

Page 29 - Log “H” front

34 Remote Control Transmitter Functions NOTE: The Wall Receiver will “beep” once every time a Remote Transmitter Key is pressed, signaling that th

Page 30

35 REMOTE TRANSMITTER OPERATING INSTRUCTIONS TO TURN ON THE APPLIANCE: 1. Press the ON/OFF button. The transmitter display will show all active

Page 31

36 MANUAL BYPASS OF THE REMOTE SYSTEM If the remote transmitter is misplaced or lost, the appliance can be turned on manually by sliding the three

Page 32

37 “FIRST TIME” PILOT LIGHTING INSTRUCTIONS IMPORTANT: Be sure all items on "INSTALLATION CHECK OFF LIST" in the Installation Manual hav

Page 33 - LIGHTING CHECK OFF LIST

38 Backup Batteries The life span of the backup batteries depends on the quality of the batteries used and how long the batteries have been install

Page 34 - FLAME HEIGHT KNOB

3 Contents FOR YOUR SAFETY READ BEFORE LIGHTING 1 DXV45 DT3 FEATURES - QUICK REFERENCE INFORMATION 2 INITIAL STARTUP ADVICE 2 CONTENTS 3 SPECIFI

Page 35 - ON SMART

39 BLOWER OPERATION AND WIRING WARNING: The Electrical Junction box within this appliance must be connected to a grounded LIVE power circuit. No sw

Page 36

40 TROUBLESHOOTING MENDOTA GAS DXV FIREPLACE SYMPTOM PROBABLE CAUSES CORRECTIVE ACTION 1. Thin black coating (soot) forms on viewing glass. A.

Page 37

41 CUSTOMER INFORMATION AND TROUBLE-SHOOTING MAXIMUM ALLOWABLE SURFACE TEMPERATURES Mendota Fireplaces comply with UL Standards for maximum surface

Page 38 - REMOTE TRANSMITTER

42 MAINTENANCE ANNUAL MAINTENANCE OF THIS MENDOTA FIREPLACE IS REQUIRED. The following procedures must be performed each year by a Mendota approved

Page 39

43 WIRING SCHEMATICS Note: The DXV45 DT3 ignition system utilizes Transformed DC power for normal ignition functions. In the event of a pow-er outa

Page 40

44 NATURAL TO LP GAS CONVERSION INSTRUCTIONS Kit # HA-42-00302 Mendota Model DXV45-DT3-LX This conversion kit shall be installed by a qualified ser

Page 41

45 5. Using a ½” deep well socket wrench, remove Front and Rear Orifices. HINT: PACK SOME SOFT PAPER OR INSWOOL INSIDE DEEP WELL SOCKET TO STOP

Page 42

46 . 10. Before reinstalling burners, loosen the screw that secures the rotary air shutter on the Front Burner. Rotate the air shutter open to ¼”

Page 43 - MAINTENANCE

47 INSTALLING THE LP PRESSURE REGULATOR WARNING: READ AND UNDERSTAND ALL INSTRUCTIONS PACKAGED WITH LP PRESSURE REGULATOR BODY BEFORE YOU ATTEMPT T

Page 44

48 INLET TAP OUTLET TAP LP GAS PRESSURE REQUIREMENTS Inlet and manifold gas pressure checking taps are located on gas valve. These ports are only a

Page 45 - ORIFICE SIZES REQUIREMENT:

4 HIGH ALTITUDE INSTALLATION INFORMATION: Prior to installing at altitudes higher than 7500, please con-tact the Mendota technical service departme

Page 46

49 REPLACEMENT PARTS MENDOTA DXV-45 DT3 FIREPLACE PART NO DESCRIPTION PART NO DESCRIPTION 65-02-00103 GLASS GASKET 05-04-00050 PILOT AS

Page 47

50 LISTING LABEL, RATING PLATE REPSENTATION LISTED DIRECT VENT GAS FIREPLACE HEATER POÊLE AU GAZ HOMOLOGUE’, A AÉRATION DIRECTE NOT FOR USE WITH S

Page 48

51 THIS PAGE LEFT BLANK INTENTIONALLY

Page 49

52 MENDOTA WARRANTY QUALIFICATION & SERVICE REFERENCE FORM As a part of Mendota's on-going program of customer satisfaction, this Form ver

Page 50 - MENDOTA DXV-45 DT3 FIREPLACE

53 TAPE SHUT -----------------------------------------------------------------------------------------------------------------

Page 51

54 MENDOTA EXTENDED PROTECTION AND LIMITED WARRANTY MENDOTA FV44 DIRECT VENT FIREPLACE INSERT Mendota Division of Johnson Gas Appliance Company, 5

Page 52

55 Johnson Gas Appliance Company 520 E Avenue N.W. - Cedar Rapids, IA 52405 Mendota Hearth Division www.johnsongas.com or www.mendotahearth.com

Page 53

5 CONGRATULATIONS! You are the owner of a world class, heat producing, gas, direct vent, sealed combustion fireplace. This elegant, highly efficie

Page 54

6 LOCATING THE FIREPLACE AND GENERAL INFORMATION Your Mendota Gas Fireplace has a state-of-the-art co-axial direct vent, sealed combustion system.

Page 55

7 HEATING PERFORMANCE Mendota Gas Built-in Fireplaces are true, high efficiency gas heaters. With its high heat output the Mendota Fireplace will

Page 56

8 HIGH ALTITUDE INSTALLATION INFORMATION: Prior to installing at altitudes higher than 7500, please con-tact the Mendota technical service departme

Comments to this Manuals

No comments