- 54 -
INLET
PRESSURE TAP
MANIFOLD PRESSURE
TAP
LP GAS PRESSURE REQUIREMENTS
Inlet and manifold gas pressure checking taps are located on gas valve. A qualified installer shall take pressure
surements at these ports to verify and set the correct gas pressures during the LP Kit installation.
Manifold pressure must
be taken at the “MANIFOLD PRESSURE" tap and inlet pressure at the
"INLET PRESSURE" tap
with the burner operating by a qualified installer.
DESIRED
INLET
PRESSURE
MINIMUM
INLET
PRESSURE
MAXIMUM
INLET
PRESSURE
MANIFOLD
OUTLET
PRESSURE
AIR SHUTTER
POSITION
L.P. GAS 11.0" W.C.
(2.75 kPa)
11" W.C.
(2.75 kPa)
13.0" W.C.
(3.24 kPa)
10.0" W.C.
(2.5 kPa)
1/4" OPEN MIN.
(5 mm)
TURN GAS VALVE HI-LO KNOB TO "HIGH" POSITION. OUTLET GAS PRESSURES MAY VARY PLUS OR MINUS 5%.
LPG PROPER INPUT RATES:
With the proper orifices installed, as specified above, this fireplace utilizing LP Gas will have a maximum input rate of
50,000 Btu/Hr.
LEAK TESTING REQUIREMENTS
Prior to completing the conversion process , check for gas leaks
with soap and water solution at all plumbing joints prior to plac-
ing this appliance into operation. It is recommended that all
gas-plumbing joints, factory installed and field installed are
checked for leaks.
PILOT FLAME AND MAIN BURNER RELATIONSHIP
VERIFICATION
Prior to completing the conversion process, the qualified ser-
vice technician must, light the pilot light and verify the relation-
ship between the pilot light flames and the main burners. The
pilot light flames directed towards the propagation ports on the
rear and front burner must overlap the propagation ports on the
burners. The pilot light flames must be a minimum of ¾” long and must overlap the propagation ports on both the rear and
front burners as shown in
Figure 41. Verify that the burner tubes ignite quickly and the burner flames propagate smoothly
along the entire length of the burners.
PILOT FLAME LENGTH ADJUSTMENT
If the pilot light flame length is too short or the required minimum thermopile voltage cannot be achieved using the
factory default setting of the pilot light flame length, a qualified installer may adjust the length of the pilot light
flames to meet the two requirements: Minimum Thermopile output voltage shall be 325mV and the pilot light
flames must be long enough to overlap the burner ports as shown in Figure 41.
Figure 40: Pressure Test Port
Figure 41: PILOT FLAMES AND
BURNER PORTS ALIGNMENT
PILOT
FLAME
MUST
OVERLAP
BURNER
PORTS.